Know the Code

Fire Separation Distance

Learn how the IRC addresses ways to prevent the spread of fire from one property to another.

By Glenn Mathewson Issue 319 - November 2023
  • X
  • facebook
  • linkedin
  • pinterest
  • email
  • add to favorites Log in or Sign up to save your favorite articles
Drawing: Kate Francis

Synopsis: Although most municipalities have created stricter codes for fire separation distance (FSD) than the IRC, the IRC’s provisions may become better known as density in urban and suburban areas increases and accessory dwelling units (ADUs) become more common. Glenn Mathewson, a code expert and educator, provides a detailed summary of these provisions.


In centuries past, it was much more common for cities across the globe to suffer catastrophic fires that wiped out entire neighborhoods, fortunes, and most tragically, ended lives. At the turn of the 19th century, addressing these city-wide fires was a major focus of new building codes, including provisions limiting the size, location, and distance between wood buildings. In the 2021 International Residential Code (IRC), the provisions addressing the prevention of the spread of fire from one property to another are defined as “fire separation distance” (FSD) and can be found in section R302.

Many in the building community are unfamiliar with FSD provisions because most municipalities have traditionally created their own zoning setbacks at greater distances than the separations required by FSDs. Rather than being based on fire science, zoning setbacks required by most municipalities are implemented for reasons like aesthetics, population-density goals, and property values. But looking ahead using my best fortune-telling skills, I foresee fire separation distances will become more of a discussion in home construction because of the growing trend to increase density in urban and suburban areas and due to the rising popularity of accessory dwelling units (ADUs).

The 2021 IRC defines “fire separation distance” as the distance measured from the building face to one of the following:

1. To the closest interior lot line.

2. To the centerline of a street, an alley or public way.

3. To an imaginary line between two buildings on the lot.

The distance shall be measured at a right angle from the face of the wall.

Definition 1: Lot lines

Fire is less likely to spread from one building to another if they are located more than 10 ft. from each other. But nowhere in the code does it mention keeping buildings more than 10 ft. apart. Instead, the IRC provisions split that distance and state that walls located 5 ft. or further from an interior lot line do not need special fire-resistive construction (more on this below). A 10-ft. separation between buildings and a 5-ft. separation between a building and a lot line may seem like the same thing, but it’s not. This language is specifically worded to provide equal freedom of construction to adjoining property owners and eliminates a race to be the first to build closer to the edge of a lot. If the only consideration was a 10-ft. separation between non-fire-resistive-rated walls on neighboring buildings, the first owner to build could locate their house right on the property line (zoning setbacks permitting), causing their neighbor to lose 10 ft. of buildable area on their property or require the second builder to assume all the burden and cost of fire-resistive construction. 

Most FSD applications are covered by definition #1, measuring to the interior lot line. But unlike zoning setbacks, which are measured from the lot line to the closest part of a building, FSD is measured from the building to the lot line. This language makes a difference when the walls of a dwelling might not be built perpendicular to the lot line. As shown in the drawing above, the distance from walls built at an angle in relation to the lot line is measured at right angles, which results in the corner portion of the house being closer than 5 ft. to the lot line. 

Definition 2: Public ways

The second way to measure FSD is from a face of the wall or projection to the center of a street, alley, park, or other parcel of land permanently appropriated for public use. The spirit of this definition came about because it’s unlikely that a structure would be built in the middle of a street or alley. And because the distance from the center of all of these examples to a wall would be much greater than 5 ft., this definition would not often trigger greater setbacks or fire-resistant construction. However, this means (again, zoning setbacks permitting) that it would be possible for a dwelling to be located right on the property line if that property line abutted a public right of way, like the ADU located near the alley shown in the illustration above. 

Definition 3: Imaginary lines

When two or more dwellings are built on a single lot, there is still the same potential hazard of fire spreading between these separate dwellings located closer than 10 ft. apart. Unlike many local zoning ordinances, under the IRC there is no lot-size limit and no limit to the number of dwelling units that can be built on a lot. In these cases, an “imaginary line” can be established anywhere between two dwellings. This definition has become more relevant today with the increased demand for ADUs.

For example, let’s say that you build a granny flat 8 ft. away from the main house. Drawing an imaginary line halfway between the two structures would result in 4 ft. of separation to that imaginary center line, which would create the need for fire-resistant wall assemblies on each building. However, if your imaginary line is located 5 ft. from the main house and 3 ft. from the ADU, then only the one wall on the smaller structure would need to be built with fire-­resistant provisions.    

Building within the limits

There are a few nuances not to overlook when measuring FSD. There is no FSD requirement between a dwelling and accessory buildings on the same lot, such as a detached garage, shed, or pool house. However, those accessory buildings must comply with FSD provisions as they relate to property boundaries, with the exception of sheds and play structures 200 ft. or less and not requiring a building permit.

Section and table R302.1 describe the various protections required at specific FSDs for four different elements: walls, projections, openings, and penetrations. The simple way to avoid having to understand this subject any further and avoid fire-resistant construction is to maintain a 5-ft. or greater FSD from all of these elements. If you’d like to build within the limits of an FSD and zoning setbacks won’t stop you, here’s what you need to prepare for under the model IRC.

Walls

Walls with an FSD of less than 5 ft. (and down to zero) must be built as a one-hour fire-resistance-rated assembly, which might include additional steps like installing fire-resistant drywall to both sides of the wall assembly. These assemblies must be validated through testing under ASTM E119 or UL 263, which allows for a very wide assortment of proprietary methods and materials to choose from. Another option is to use a generic assembly “recipe” listed in the International Building Code (IBC), section 703.2.2. Regardless of how the assembly is validated, it must be one that can resist fire on both sides of the wall. The building being built within the FSD is the one that must assume the responsibility to protect against the spread of any fire that could start either inside their building or from a neighboring building.

Projections

Projections are the next elements covered in the IRC, and FSD provisions get a little more complicated from this point. Historically speaking, provisions for projections have been intended to address overhanging eaves of roofs and the underside of floor cantilevers. Though often attempts are made by building authorities to apply projection provisions to features like attached decks or porch roofs, the current provisions quite simply were never designed to address those features. This is a subject where future code development islikely to occur, and local amendments, interpretations, and requirements can be expected.

The wall on a cantilevered projection like a fireplace chase with an FSD of less than 5 ft. is treated the same as any other wall and needs to be protected with one-hour fire resistance. However, the bottom surface of the cantilevered projection is treated like an eave. The bottom side of cantilevered structures and eaves (the soffit area) with an FSD less than 5 ft. but more than 2 ft. must be protected with one-hour fire resistance, fire-retardant-treated wood, or heavy-timber construction. An FSD of less than 2 ft. measured to the face of the projection is not permitted except for one specific exception found in section R302.1. On a detached garage, eave projections can be less than the 2-ft. FSD provided they do not project more than 4 in. from the exterior wall.

But that’s not the end of the story with eaves, as we must look at the footnotes to table 302.1. These footnotes allow for no fire protection under eaves that have no ventilation openings, and this is due to the role vented eave projections play in the spread of fire. Soffit vents on the underside of eaves are common for attic ventilation, as they draw air in from the lower side of the roof, while upper openings allow hot and humid air to escape. This natural thermocycling is a mechanism for pulling burning embers and hot gases into the attic, one of the most common ways fire has historically spread between buildings. Of course, this creates the conundrum in that if your eaves are vented, they need to be protected with one-hour fire resistance, but if your eaves are protected with one-hour fire resistance, they no longer have the ability to vent an attic above that portion of the wall.

The second footnote in table R302.1 allows unprotected projections of eave rake edges provided that the gable wall below the eave does not have a gable vent. This footnote exception to protection is a little harder to explain in a sensible way. A vent opening in a gable-end wall would first be regulated as an opening (the next element of FSD to discuss), but its role in spreading fire through attic ventilation is unique compared to typical wall openings. So provided your gable-end wall does not have a vent opening, no protection of the eave above is required. But heads up: Jurisdictions across the U.S. have removed the footnote for gable-wall ventilation in their code adoption, as they too have difficulty making sense of it.

Openings

The next element under FSD is openings in walls, but it’s critical not to think of this as just an opening that allows the passage of fire, like a door, operable window, or vent opening. It’s about breaks and gaps in standard wall assemblies, so even a fixed-glass transom window would apply. Openings are only allowed in walls with an FSD no less than 3 ft., and the openings are limited to 25% of the total wall area for all openings. Like all FSD elements, once a 5-ft. FSD is reached there are no requirements. The idea here is that a window and other openings could allow radiant heat from a nearby fire to travel into a home more quickly than it would through a standard wall assembly.

To assist in clarifying how to apply this maximum percentage, a proposal was submitted for the 2024 IRC which would specify that the 25% of wall area would apply to each story, not the entire wall. Using just windows as an example, the concern is that if the entire 25% opening allowance on a two-story wall is placed on the top story alone, 50% of the space on that top story will be comprised of windows, greatly reducing its ability to resist radiant heat. I was surprised that this proposal was not approved.

One opening exception to note is that foundation vents are not limited to the minimum 3-ft. FSD and are not included in the 25% area limit. Being low to the ground, these vents have not provided any evidence of fire-spread risk sufficient to prohibit them.

Seperation Strategies

Knowing when to use fire-resistive assemblies and provisions means understanding the nuances of fire separation distance (FSD). The following assumes no conflict with local zoning setbacks.

Fire Separation Distance
Drawing: Kate Francis

1. Walls located 5 ft. or more from a lot line do not require fire-resistive construction.

2. The bottom side of unvented eaves/soffits need fire-resistive protection when closer than 5 ft. to a lot line.

3.FSDs may not apply to projections like decks and porch roofs—talk to your local building official.

4. No FSD is required on tool or storage sheds or play structures 200 sq. ft. or less.

5. A FSD of 5 ft. is required between lot lines and accessory buildings.

6. An imaginary line can be used to measure the FSD between a primary dwelling and an ADU (fire protection will be required on any structure within 5 ft. of the imaginary line).

7. No FSD is required between dwellings and accessory buildings on the same lot.

8. FSDs measured to the center of a public street could result in a dwelling being located closer than 5 ft. from the lot line.

9. FSD is measured perpendicular from the wall to the lot line, which could result in a setback of less than 5 ft.

Penetrations

Finally, penetrations are addressed. These are items that go through a wall but are not openings. This includes elements like hose bibs, receptacle-outlet boxes, furnace vents, and clothes-dryer exhaust. There are no FSD protection requirements until these items have an FSD of less than 3 ft. In those instances, the penetration must be protected in accordance with section R302.4. This section provides details for penetrations of dwelling unit separation walls, including specific details outside the scope of this article. In most cases an approved penetration firestop system compliant to ASTM 814 or UL 1479 will be required. This usually results in the use of “fire caulk” installed in the annular space around the penetrating item, but that is a summarized generalization of a much more in-depth topic.

Discussions continue

To accommodate the rising popularity of residential fire-sprinkler systems, table R302.1(2) provides reduced protections of the four elements when a home is protected by a sprinkler system, but those details are not provided in this article. As previously mentioned, the footnotes relating to attic ventilation and projection protection are questioned by many in the building community, as are the inconsistency and the guesswork in the enforcement of FSD provisions as they relate to decks and porch roofs. I expect these subjects will be discussed in the hearings for the 2027 IRC, and I am looking forward to taking part in that exchange.

Glenn Mathewson is a consultant and educator with BuildingCodeCollege.com.

From Fine Homebuilding #319


RELATED STORIES

  • The (Often Painful) Evolution of Residential Fire Sprinklers
  • Taping Drywall for Fire Safety
  • 7 Common Fireblocking Locations

Sign up for eletters today and get the latest how-to from Fine Homebuilding, plus special offers.

Signing you up...

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
See all newsletters
See all newsletters
×

Get home building tips, offers, and expert advice in your inbox

Signing you up...

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
See all newsletters
See all newsletters

New Feature

Fine Homebuilding Forums

Ask questions, offer advice, and share your work

  • X
  • facebook
  • linkedin
  • pinterest
  • email
  • add to favorites Log in or Sign up to save your favorite articles

Log in or create an account to post a comment.

Sign up Log in

Become a member and get full access to FineHomebuilding.com

More Know the Code

View All
  • Hazard-Free Hot Tubs
  • The Right Spots for Smoke Alarms
  • Stairway Basics
  • How Far Can Deck Joists Cantilever?
View All

Up Next

Video Shorts

Featured Story

Tools and Gear for the Moms Who Get it Done

From work boots to power tools, these favorite picks make perfect gifts for moms and women who build.

Featured Video

How to Install Cable Rail Around Wood-Post Corners

Use these tips to keep cables tight and straight for a professional-looking deck-railing job.

Related Stories

  • Hazard-Free Hot Tubs
  • Eight Common Electrical Myths and Mistakes
  • The Right Spots for Smoke Alarms
  • Building Confidence, Community, and Inclusive Trades

Discussion Forum

Recent Posts and Replies

  • |
  • |
  • |
  • |
  • |
  • |
View More Create Post

Highlights

Fine Homebuilding All Access
Fine Homebuilding Podcast
Tool Tech
Plus, get an extra 20% off with code GIFT20

Video

View All Videos
  • HVAC and Indoor-Air Quality
  • Meet Current Energy Codes with Continuous Insulation
  • Combat Extreme Weather With a FORTIFIED Roof
  • Vents for Wildfire Protection
View All

Building Codes

View All Building Codes Articles
  • Building Codes Meet Building Science
  • The Inflation Reduction Act: A Year of Tax Credit Claims in Review
  • The Performance Paths to the Energy Codes
View All Building Codes Articles

Fine Homebuilding Magazine

  • Issue 331 - June 2025
    • A More Resilient Roof
    • Tool Test: You Need a Drywall Sander
    • Ducted vs. Ductless Heat Pumps
  • Issue 330 - April/May 2025
    • Deck Details for Durability
    • FAQs on HPWHs
    • 10 Tips for a Long-Lasting Paint Job
  • Issue 329 - Feb/Mar 2025
    • Smart Foundation for a Small Addition
    • A Kominka Comes West
    • Making Small Kitchens Work
  • Issue 328 - Dec/Jan 2024
    • How a Pro Replaces Columns
    • Passive House 3.0
    • Tool Test: Compact Line Lasers
  • Issue 327 - November 2024
    • Repairing Damaged Walls and Ceilings
    • Plumbing Protection
    • Talking Shop

Fine Home Building

Newsletter Sign-up

  • Fine Homebuilding

    Home building tips, offers, and expert advice in your inbox.

  • Green Building Advisor

    Building science and energy efficiency advice, plus special offers, in your inbox.

  • Old House Journal

    Repair, renovation, and restoration tips, plus special offers, in your inbox.

Signing you up...

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
See all newsletters

Follow

  • Fine Homebuilding

    Dig into cutting-edge approaches and decades of proven solutions with total access to our experts and tradespeople.

    Start Free Trial Now
    • Facebook
    • Instagram
    • X
    • LinkedIn
  • GBA Prime

    Get instant access to the latest developments in green building, research, and reports from the field.

    Start Free Trial Now
    • Facebook
    • YouTube
  • Old House Journal

    Learn how to restore, repair, update, and decorate your home.

    Subscribe Now
    • Facebook
    • Instagram
    • X
  • Fine Homebuilding

    Dig into cutting-edge approaches and decades of proven solutions with total access to our experts and tradespeople.

    Start Free Trial Now
    • Facebook
    • Instagram
    • X
    • LinkedIn
  • GBA Prime

    Get instant access to the latest developments in green building, research, and reports from the field.

    Start Free Trial Now
    • Facebook
    • YouTube
  • Old House Journal

    Learn how to restore, repair, update, and decorate your home.

    Subscribe Now
    • Facebook
    • Instagram
    • X

Membership & Magazine

  • Online Archive
  • Start Free Trial
  • Magazine Subscription
  • Magazine Renewal
  • Gift a Subscription
  • Customer Support
  • Privacy Preferences
  • About
  • Contact
  • Advertise
  • Careers
  • Terms of Use
  • Site Map
  • Do not sell or share my information
  • Privacy Policy
  • Accessibility
  • California Privacy Rights

© 2025 Active Interest Media. All rights reserved.

Fine Homebuilding receives a commission for items purchased through links on this site, including Amazon Associates and other affiliate advertising programs.

  • Home Group
  • Antique Trader
  • Arts & Crafts Homes
  • Bank Note Reporter
  • Cabin Life
  • Cuisine at Home
  • Fine Gardening
  • Fine Woodworking
  • Green Building Advisor
  • Garden Gate
  • Horticulture
  • Keep Craft Alive
  • Log Home Living
  • Military Trader/Vehicles
  • Numismatic News
  • Numismaster
  • Old Cars Weekly
  • Old House Journal
  • Period Homes
  • Popular Woodworking
  • Script
  • ShopNotes
  • Sports Collectors Digest
  • Threads
  • Timber Home Living
  • Traditional Building
  • Woodsmith
  • World Coin News
  • Writer's Digest
Active Interest Media logo
X
X
This is a dialog window which overlays the main content of the page. The modal window is a 'site map' of the most critical areas of the site. Pressing the Escape (ESC) button will close the modal and bring you back to where you were on the page.

Main Menu

  • How-To
  • Design
  • Tools & Materials
  • Video
  • Blogs
  • Forum
  • Project Guides
  • Reader Projects
  • Magazine
  • Members
  • FHB House

Podcasts

  • FHB Podcast
  • ProTalk

Webinars

  • Upcoming and On-Demand

Podcasts

  • FHB Podcast
  • ProTalk

Webinars

  • Upcoming and On-Demand

Popular Topics

  • Kitchens
  • Business
  • Bedrooms
  • Roofs
  • Architecture and Design
  • Green Building
  • Decks
  • Framing
  • Safety
  • Remodeling
  • Bathrooms
  • Windows
  • Tilework
  • Ceilings
  • HVAC

Magazine

  • Current Issue
  • Past Issues
  • Magazine Index
  • Subscribe
  • Online Archive
  • Author Guidelines

All Access

  • Member Home
  • Start Free Trial
  • Gift Membership

Online Learning

  • Courses
  • Project Guides
  • Reader Projects
  • Podcast

More

  • FHB Ambassadors
  • FHB House
  • Customer Support

Account

  • Log In
  • Join

Newsletter

Get home building tips, offers, and expert advice in your inbox

Signing you up...

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
See all newsletters
See all newsletters

Follow

  • X
  • YouTube
  • instagram
  • facebook
  • pinterest
  • Tiktok

Join All Access

Become a member and get instant access to thousands of videos, how-tos, tool reviews, and design features.

Start Your Free Trial

Subscribe

FHB Magazine

Start your subscription today and save up to 81%

Subscribe

We hope you’ve enjoyed your free articles. To keep reading, become a member today.

Get complete site access to expert advice, how-to videos, Code Check, and more, plus the print magazine.

Start your FREE trial

Already a member? Log in

Privacy Policy Update

We use cookies, pixels, script and other tracking technologies to analyze and improve our service, to improve and personalize content, and for advertising to you. We also share information about your use of our site with third-party social media, advertising and analytics partners. You can view our Privacy Policy here and our Terms of Use here.

Cookies

Analytics

These cookies help us track site metrics to improve our sites and provide a better user experience.

Advertising/Social Media

These cookies are used to serve advertisements aligned with your interests.

Essential

These cookies are required to provide basic functions like page navigation and access to secure areas of the website.

Delete My Data

Delete all cookies and associated data